Driving method Continuous commercial power supply system (line interactive)
housing Stationary type (thin/with vertical stand)
Rated input voltage [100Vmode]AC90~110V、[110Vmode]AC100~120V、[115Vmode]AC105~125V、[120Vmode]AC110~130V
Rated input frequency 50/60Hz±4Hz
Number of input phases Single-phase 2-wire
Input outlet shape NEMA5-15P
Rated output voltage: During commercial operation: input voltage through output. During backup operation: [100Vmode] AC90 to 110V, [110Vmode] AC100 to 120V, [115Vmode] AC105 to 120V, [120Vmode] AC105 to 120V
Rated output frequency: During commercial operation: input frequency through output.
Number of output phases Single-phase 2-wire
Output outlet shape NEMA5-15R
Number of output outlets (backup) 2
Number of output outlets (through) 0
Power consumption (normal/maximum) 10W/20W
Maximum output capacity (W) 300W
Maximum output capacity (VA) 500VA
Backup time (at full load) 3 points
Output voltage during battery operation 100V
Output frequency during battery operation 50/60Hz±1Hz
Output waveform during battery operation square wave
Switch-to-battery time Within 10msec
battery type Sealed lead battery (long life type)
number of batteries 1
charging time 12
Power management software (attached software) Yes PowerAct Pro (automatic shutdown software) and UPS service driver
Power management software compatible OS Windows Server2003、XP、2000、Me、98、Linux/Windows Server2003、XP、2000
Surge function Yes Power supply noise/lightning surge protection
Safety Specifications VCCI Class B, UL1778, CE marking
Body size (H×W×D) 45×287×287
body weight 5kg
remarks 3-year free warranty (battery 3-year free service included) 10 regulated chemical substances non-containment certificate can be issued
asbestos does not contain
RoHS Directive incompatible
J-Moss Not applicable
Environmental self-assertion mark none
Other environmental and safety standards WL 1778/h
Radio Law Remarks: Non-target: Because it does not emit radio waves
Telecommunications Business Law Remarks: Not applicable: Not connected to public lines
radio wave method non-target
Telecommunications Business Law non-target
Legal related confirmation date 20150213
Electrical Appliance and Material Safety Law (body) non-target
Electrical Appliance and Material Safety Law (accessories, etc.) Conformance/Exception Approval
Electrical Appliance and Material Safety Law (remarks): Body: Not applicable 3P-2P conversion plug (accessory): Compliant