Driving method Regular inverter power supply system
housing rack mount type
Rated input voltage AC100V/110V/115V/120V
Rated input frequency 50/60Hz±4Hz
Number of input phases Single-phase 2-wire
Input outlet shape 3P (NEMA L5-30P)/terminal block
Rated output voltage: 100Vmode: AC100V±3% 110Vmode: AC110V±3% 115Vmode: AC115V±3% 120Vmode: AC120V±3%
Rated output frequency Synchronized to input frequency
Number of output phases Single-phase 2-wire
Output outlet shape NEMA 5-20R (common for 15A)
Number of output outlets (backup) 6
Number of output outlets (through) 0
Power consumption (normal/maximum) 410W/540W
Maximum output capacity (W) 2400W
Maximum output capacity (VA) 3000VA
Backup time (at full load) 4 points
Output voltage during battery operation 100V
Output frequency during battery operation 50/60Hz±1Hz
Output waveform during battery operation sine wave
Switch-to-battery time no interruption
battery type Sealed lead battery (DC12V/8Ah)
number of batteries 6
charging time 8 hours
Power management software (attached software) Yes (PowerAct Pro, UPS Service Driver, UPS Power Manager)
Power management software compatible OS: Windows/Linux/Mac *Intel Mac is not supported. For Intel Mac, please use SNMP/Web card SC20G
Surge function Yes Power supply noise/lightning surge protection
Safety Specifications Conforming to UL1778/CE marking
Body size (H×W×D) 438(W)×550(D)×130(H)mm
body weight 33Kg
remarks Please fax back the service application form included with the product, or send us a user registration (postcard).
asbestos does not contain
RoHS Directive Correspondence
J-Moss Not applicable
Environmental self-assertion mark none
Other environmental and safety standards
Radio Law Remarks: Not applicable: Because it does not emit radio waves
Telecommunications Business Law Remarks: Not applicable: Not connected to public lines
Electrical Appliance and Material Safety Law Remarks: Out of scope: Power cable lacks versatility
radio wave method non-target
Telecommunications Business Law non-target
Electrical Appliance and Material Safety Law non-target
Legal related confirmation date 20150213