OMRON
OMRON POWLI BU300RWG6 [UPS BU300RW + free warranty 6Y]
Regular price
$5,976.51 USD
Regular price
$6,291.06 USD
Sale price
$5,976.51 USD
Unit price
/
per
Driving method | Regular inverter power supply system |
---|---|
housing | rack mount type |
Rated input voltage | AC100V/110V/115V/120V |
Rated input frequency | 50/60Hz±4Hz |
Number of input phases | Single-phase 2-wire |
Input outlet shape | 3P (NEMA L5-30P)/terminal block |
Rated output voltage: 100Vmode: AC100V±3% 110Vmode: AC110V±3% 115Vmode: AC115V±3% 120Vmode: AC120V±3% | |
Rated output frequency | Synchronized to input frequency |
Number of output phases | Single-phase 2-wire |
Output outlet shape | NEMA 5-20R (common for 15A) |
Number of output outlets (backup) | 6 |
Number of output outlets (through) | 0 |
Power consumption (normal/maximum) | 410W/540W |
Maximum output capacity (W) | 2400W |
Maximum output capacity (VA) | 3000VA |
Backup time (at full load) | 4 points |
Output voltage during battery operation | 100V |
Output frequency during battery operation | 50/60Hz±1Hz |
Output waveform during battery operation | sine wave |
Switch-to-battery time | no interruption |
battery type | Sealed lead battery (DC12V/8Ah) |
number of batteries | 6 |
charging time | 8 hours |
Power management software (attached software) | Yes (PowerAct Pro, UPS Service Driver, UPS Power Manager) |
Power management software compatible OS: Windows/Linux/Mac *Intel Mac is not supported. For Intel Mac, please use SNMP/Web card SC20G | |
Surge function | Yes Power supply noise/lightning surge protection |
Safety Specifications | Conforming to UL1778/CE marking |
Body size (H×W×D) | 438(W)×550(D)×130(H)mm |
body weight | 33Kg |
remarks | Please fax back the service application form included with the product, or send us a user registration (postcard). |
asbestos | does not contain |
RoHS Directive | Correspondence |
J-Moss | Not applicable |
Environmental self-assertion mark | none |
Other environmental and safety standards | |
Radio Law Remarks: Not applicable: Because it does not emit radio waves | |
Telecommunications Business Law Remarks: Not applicable: Not connected to public lines | |
Electrical Appliance and Material Safety Law Remarks: Out of scope: Power cable lacks versatility | |
radio wave method | non-target |
Telecommunications Business Law | non-target |
Electrical Appliance and Material Safety Law | non-target |
Legal related confirmation date | 20150213 |